Add to Cart
For DC photovoltaic cables
For AC photovoltaic cables
Properties such as moisture and heat resistance, high and low temperature resistance, acid and alkali resistance,ozone resistance, UV resistance, flame retardancy, etc
Pipe laying, shallow trench laying, cable trench laying, tunnel laying, interlayer laying, supported overhead laying, suspended overhead laying, etc.
Cross section(mm²) |
Conductor Construction(no/mm) |
Conductor Stranded OD.max(mm) |
Cable OD.(mm) |
Approximate weight of cable |
Max Cond Resistance(Ω/km,20°C) |
1×1.5 |
48/0.20 |
1.58 |
4.8 |
35 |
13.7 |
1×2.5 |
77/0.20 |
2.02 |
5.2 |
47 |
8.21 |
1×4 |
56/0.285 |
2.46 |
5.7 |
64 |
5.09 |
1×6 |
84/0.285 |
3.01 |
6.3 |
86 |
3.39 |
1×10 |
77/0.40 |
4.1 |
7.2 |
128 |
1.95 |
1×16 |
7×17/0.40 |
5.5 |
8.9 |
196 |
1.24 |
1×25 |
7×27/0.40 |
6.7 |
10.7 |
299 |
0.795 |
1×35 |
7×38/0.40 |
8.2 |
12.4 |
407 |
0.565 |
1×50 |
19×20/0.40 |
10.0 |
14.6 |
571 |
0.393 |
1×70 |
19×28/0.40 |
11.6 |
16.4 |
773 |
0.277 |
1×95 |
19×38/0.40 |
13.5 |
18.5 |
1024 |
0.210 |
1×120 |
24×38/0.40 |
14.4 |
19.8 |
1266 |
0.164 |
1×150 |
30×38/0.40 |
16.2 |
22.2 |
1584 |
0.132 |
1×185 |
37×38/0.40 |
18.2 |
25.0 |
1967 |
0.108 |
1×240 |
48×38/0.40 |
20.6 |
27.8 |
2518 |
0.0817 |
Installation method |
Single cable in air |
Single cable on object surface |
Two contacting cables on object surface |
Cross section(mm²) |
Carrying capacity(A) |
||
1.5 |
30 |
29 |
24 |
2.5 |
41 |
39 |
33 |
4 |
55 |
52 |
44 |
6 |
70 |
67 |
57 |
10 |
98 |
93 |
79 |
16 |
132 |
125 |
107 |
25 |
176 |
167 |
142 |
35 |
218 |
207 |
176 |
50 |
276 |
262 |
221 |
70 |
347 |
330 |
278 |
95 |
416 |
395 |
333 |
120 |
488 |
464 |
390 |
150 |
566 |
538 |
453 |
185 |
644 |
612 |
515 |
240 |
775 |
736 |
620 |
Operation temperature |
120℃ |
||
Ambient temperature |
60℃ |
Ambient temperature(℃)(air) |
≦60 |
70 |
80 |
90 |
100 |
110 |
Correction factor |
1 |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |