Add to Cart
The cables for energy supply are installed in open air, in underground, indoors, in cable ducts, power stations, residental connections and street lighting as well as in subscriber networks, where mechanical damages are not be expected.
Feature
Specification
Nominal section area |
Approx. overall diameter |
Approx. weight of cable |
Maximum DC resistance of the conductor |
||
mm2 |
mm |
kg/km |
Ω/km |
||
|
|
Cu |
Al |
20℃ Cu |
20℃ Al |
4×1.5 RE |
11.4 |
177 |
– |
12.1 |
– |
4×2.5 RE |
12.4 |
226.9 |
164.7 |
7.41 |
12.1 |
4×4 RE |
14.5 |
320.2 |
220.7 |
4.61 |
7.41 |
4×6 RE |
15.7 |
424.1 |
274.9 |
3.08 |
4.61 |
4×10 CC |
18.2 |
607.6 |
358.9 |
1.83 |
3.08 |
4×16 CC |
20.6 |
861 |
463.1 |
1.15 |
1.91 |
4×25 CC |
24.5 |
1287.4 |
665.6 |
0.727 |
1.2 |
4×35 CC |
26.9 |
1687.4 |
816.9 |
0.524 |
0.868 |
4×50 SM |
28 |
2295.4 |
1051.8 |
0.387 |
0.641 |
4×70 SM |
31.6 |
3095.1 |
1354.1 |
0.268 |
0.443 |
4×95 SM |
35.9 |
4146 |
1783.2 |
0.193 |
0.32 |
4×120 SM |
38.5 |
5125.7 |
2141.1 |
0.153 |
0.253 |
4×150 SM |
42.8 |
6379.9 |
2649.2 |
0.124 |
0.206 |
4×185 SM |
48.4 |
7849.2 |
3248 |
0.0991 |
0.164 |
4×240 SM |
53.5 |
10084 |
4114.8 |
0.0754 |
0.125 |
4×300 SM |
59.2 |
12526.3 |
5064.8 |
0.0601 |
0.1 |